Filter&Fans

Combining All Three: Louver cover+Filter+Fan
-
Cooling Efficiency: The louver cover ensures passive airflow, while the fan provides active cooling, and the filter ensures that only clean, unblocked air flows into the enclosure.
-
Environmental Protection: By combining a filter and louver cover, you can protect the internal components from dust, dirt, moisture, and other environmental factors while ensuring proper ventilation.
How Filter&Fans works

Principle:
- Utilize the difference in physical properties between cold air and hot air. Hot air has a lower density and rises to be discharged outside the cabinet.
- Forced ventilation through fans forms a circulation system. The fans inhale cold air and discharge hot air.
- The filter prevents dust and particles from entering, keeping the air inside the cabinet clean.
Product Parameters

| Fan Option | ||||
|---|---|---|---|---|
| Product number | VK116.230 | VK116.115 | VK116.24 | |
| Axial Fan | ZF-92S-230 | ZF-92S-115 | ZF-92B-024 | |
| Operating Voltage(V/Hz) | 230/50/60 | 115/50/60 | 24(DC) | |
| Air flow,free blowing | 20/25m³/h | 20m³/h | ||
| Air flow,with outlet filter | 15/18m³/h | |||
| Axial fan | Axial auto start shaded pole motor | |||
| Rated current(A) | 0.07/0.06 | 0.12/0.10 | 0.18 | |
| Power(W) | 11/13 | 11/13 | ||
| Noise level(dB) | 38/43 | |||
| working temperature | -10℃~+55℃ | |||
| Material | ABS | |||
| Flammability rating | UL94-V0 | |||
| Protection class | IP 54 | |||

| Fan Option | ||||
|---|---|---|---|---|
| Product number | VK148.230 | VK148.115 | VK148.24 | |
| Axial Fan | ZF-120S-230 | ZF-120S-115 | ZF-120B-024 | |
| Operating Voltage(V/Hz) | 230/50/60 | 115/50/60 | 24(DC) | |
| Air flow,free blowing | 55/56m³/h | |||
| Air flow,with outlet filter | 1*TK VK148:43/50m³/h 2*TK VK148:48/58m³/h | |||
| Axial fan | Axial auto start shaded pole motor | DC motor | ||
| Rated current(A) | 0.12/0.10 | 0.24/0.20 | 0.30 | |
| Power(W) | 19/14 | 18/15 | 3.5 | |
| Noise level(dB) | 50/52 | |||
| working temperature | -10℃~+55℃ | |||
| Material | ABS | |||
| Flammability rating | UL94-V0 | |||
| Protection class | IP 54 | |||

| Fan Option | |||
|---|---|---|---|
| Product number | VK204.230 | VK204.115 | VK204.24 |
| Axial Fan | ZF-120S-230 | ZF-120S-115 | ZF-120B-024 |
| Operating Voltage(V/Hz) | 230/50/60 | 115/50/60 | 24(DC) |
| Air flow,free blowing | 55/56m³/h | ||
| Air flow,with outlet filter | 1*VK204:71/82m³/h 2*VK204:85/98m³/h | ||
| Axial fan | Axial auto start shaded pole motor | DC motor | |
| Rated current(A) | 0.12/0.10 | 0.24/0.20 | 0.30 |
| Power(W) | 19/14 | 18/15 | 3.5 |
| Noise level(dB) | 50/52 | ||
| working temperature | -10℃~+55℃ | ||
| Material | ABS | ||
| Flammability rating | UL94-V0 | ||
| Protection class | IP 54 | ||

| Fan Option | |||
|---|---|---|---|
| Product number | VK255.230 | VK255.115 | VK255.24 |
| Axial Fan | ZF-160S-230 | ZF-160S-115 | ZF-150B-024 |
| Operating Voltage(V/Hz) | 230/50/60 | 115/50/60 | 24(DC) |
| Air flow,free blowing | 55/56m³/h | ||
| Air flow,with outlet filter | 1*VK204:170/205m³/h 2*VK204:200/230m³/h | ||
| Axial fan | Axial auto start shaded pole motor | DC motor | |
| Rated current(A) | 0.26/0.20 | 0.51/0.42 | 0.42 |
| Power(W) | 37/33 | 40/35 | 14 |
| Noise level(dB) | 48/52 | ||
| working temperature | -10℃~+55℃ | ||
| Material | ABS | ||
| Flammability rating | UL94-V0 | ||
| Protection class | IP 54 | ||

| Fan Option | ||
|---|---|---|
| Product number | VK323.230 | VK323.115 |
| Axial Fan | ZF-260S-230 | ZF-260S-115 |
| Operating Voltage(V/Hz) | 230/50/60 | 115/50/60 |
| Air flow,free blowing | 500/560m³/h | |
| Air flow,with outlet filter | VK323:360/390m³/h | |
| Axial fan | Capacitor motor | |
| Rated current(A) | 0.29/0.33 | 0.61/0.63 |
| Power(W) | 65/77 | 61/71 |
| Noise level(dB) | 62/64 | |
| working temperature | -10℃~+55℃ | |
| Material | ABS | |
| Flammability rating | UL94-V0 | |
| Protection class | IP 54 | |